Description
Product Key Feature’s:
Auto-changeover
Sleep timer
Economy mode
Up/down swing flaps
Automatic fan speed
Powerful mode
Record R32 A+++ SCoP
Save Power human sensor
Program timer + Weekly timer
Slim construction 215mm
Pipe runs up to 15 metres
Low noise – 21dBA on low
Back-up switch for loss of controller
Cold draft prevention on heat pump start up
Fault diagnosis
Auto re-start after power interruption
PRE-CHARGED WITH REFRIGERANT for up to 15 metres pipe length
DegLow ambient tested to -15/C in heating.
Light weight noise absorbing outdoor unit
Technical Data:
Model No. | Indoor unit | ASYG09KGTB | ||
Outdoor unit | AOYG09KGCA | |||
Power Source | Single-phase, ~230V, 50Hz | |||
Capacity | Cooling | kW | 2.50 | |
Heating | 2.80 | |||
UK Total/Sensible Cooling | kW | 2.74/2.51 | ||
Input Power | Cooling/Heating | kW | 0.555/0.560 | |
EER | Cooling | W/W | 4.50 | |
COP | Heating | 5.00 | ||
Pdesign | Cooling/Heating(-10°C) | kW | 2.5/2.4 | |
SEER | Cooling | W/W | 8.52 | |
SCOP | Heating (Average) | 5.11 | ||
(QHUJ (IÀFLHQFClass | Cooling | A+++ | ||
Heating (Average) | A+++ | |||
Annual Energy Consumption | Cooling | kWh/a | 103 | |
Heating | 658 | |||
Moisture Removal | I/h | 1.3 | ||
Sound Pressure Level | Indoor (Cooling) | H/M/L/Q | dB(A) | 40/34/29/19 |
Indoor (Heating) | H/M/L/Q | 42/36/31/21 | ||
Outdoor(Cooling/Heating) | High | 46/48 | ||
Sound Power Level | Indoor(Cooling/Heating) | High | 55/57 | |
Outdoor(Cooling/Heating) | High | 61/63 | ||
$LUÁRZ 5DWH | Indoor / Outdoor | High | m3/h | 700/1610 |
Net Dimensions H x W x D Weight | Indoor | mm | 270×834×215 | |
kg | 10 | |||
Outdoor | mm | 542×799×290 | ||
kg | 30 | |||
Remote Controller Type (Supplied With Unit) | Wireless | |||
Interconnecting Cable (Suggested cable size 1.5mm) | 3 Core + Earth | |||
Suggested MCB Size | Amp | 10 | ||
Max. Operating Current | Cooling/Heating | A | 6.5/9.0 | |
Power Supply To | Outdoor | |||
Connection Pipe Diameter (Gas & Liquid) | Inch | 3/8 & 1/4 | ||
Max Pipe Length (Pre-Charge) | m | 20 (15) | ||
Max Height Difference | 15 | |||
Operation Range | Cooling | °CDB | -10 to 46 | |
Heating | -15 to 24 | |||
Refrigerant | Type | R32 | ||
Charge | g | 750 | ||
Additional Charge | g/m | 20 | ||
Reviews
There are no reviews yet.