Mitsubishi Heavy Industries FDUM140VH-FDC140VNA-W MICRO INVERTER High Statics

£3,259.00

Mitsubishi Heavy Industries Air Conditioning MICRO INVERTER High Statics Ducted FDUM140VH-FDC140VNA-W 14Kw/48000Btu A++ R32

Key Benefits of the Mitsubishi FDU Ducted Heat Pumps:
Ideal for Concealed Cooling: These units are great for installations where the system needs to be hidden or blended with the room’s decor. Their slimline design makes them unobtrusive, ideal for multiple area applications or irregularly shaped rooms.
Quiet and Efficient Operation: The use of large diameter fans ensures optimal air volume while maintaining low sound levels. This makes the FDU systems a great choice for spaces where noise reduction is a priority, such as offices or bedrooms.
Advanced DC Motor Control: The automatic airflow control feature allows the system to self-adjust to maintain the rated airflow volume. By sensing external static pressure, the indoor unit adapts to keep the air flow steady for optimal performance.
Condensate Pump & Optional Return Plenums: A condensate pump comes with the unit for easier drainage, while return plenums with filters are available as an option to simplify installation and enhance system efficiency.
Variety of Capacities: With a range of capacities (from 7.1kW to 14kW), the FDU series offers flexibility to meet the specific cooling or heating needs of different spaces. Whether it’s a small room or a larger commercial area, these systems have you covered.
AirZone Multi-Zone Compatibility: This system can integrate seamlessly with the AirZone multi-zone controller, allowing you to control temperature in multiple rooms or zones independently. Perfect for larger residential setups or commercial spaces where different areas require different temperatures.
Superior Control with the RC-EX1A Controller:
Comprehensive Control: The RC-EX1A is a sophisticated multi-function controller that provides more than just basic operations. It includes:
Temperature setting, fan speed selection, mode, and timers.
Service Data Functions: Provides real-time data such as inverter compressor speed, fault diagnostics, and operational history to ensure smooth system performance and quick troubleshooting.
7-Day Programmable Timer:
Offers two on/off settings for each day, allowing for flexible scheduling.
Different temperature settings can be programmed for each period, which is ideal for saving energy or maintaining comfort at specific times.
Additional Features:
Low Ambient Control: Ensures the unit operates efficiently even in cooler conditions, making it suitable for year-round use.
Auto Restart: The system will automatically restart after a power interruption, so you don’t have to worry about manually resetting it after a blackout.
External Timer/8MS Switching for Grouping: Can synchronize up to 16 units for more seamless control across larger systems or multi-unit installations.
Key Features Recap:
7-Day programmable timer with two on/off settings.
Condensate lift pump for ease of installation.
Auto restart after power failure.
Wall-mounted controller with integrated temperature sensor.
Compatible with multi-zone systems and external controllers.

Category: Tags: , , , Product ID: 31175

Description

FDUM Technical Specification:

INDOOR UNITFDU140VH
HARD WIRED CONTROLLERRC-EX3A
OUTDOOR UNITFDC140VNA-W
UK CoolingkW12.76
UK Sensible CoolingkW10.99
Cooling Range (Nominal)kW5.0 to 14.5
S.E.E.R, EER, Energy Label5.30, 2.65, N/A
Heating Range (Nominal)kW4.0 to 16.5
S.C.O.P, COP, Energy Label4.01, 3.68, N/A
INDOOR UNITINDOOR UNIT
Exterior Dimensions (H x W x D)*mm280 x 1,370 x 740
Net Weightkg54
Air Flow (H/M/L) Coolingm3/m35 / 28 / 22
Air Flow (H/M/L) Heatingm3/m35 / 28 / 22
Sound Pressure Level (H/M/L) Coolingdb(A)40 / 35 / 30
Sound Pressure Level (H/M/L) Heatingdb(A)40 / 35 / 30
OUTDOOR UNITOUTDOOR UNIT
Exterior Dimensions (H x W x D)mm845 x 970 x 370
Net Weightkg77
Sound Pressure Level Cooling/Heatingdb(A)54 / 58
ELECTRICAL DATAELECTRICAL DATA
Power Source Rating MCBA32
Mains Power ToOutdoor1  Phase  220-240V,
50Hz
Interconnecting Wires (Dia)(mm2)3+E (1.5)
Start Current / Max Running CurrentA5 / 27
INSTALLATION/REFRIGERANTINSTALLATION/REFRIGERANT
Ref. Piping Size o.d.ins (mm)Liquid3/8
Suction5/8
Ref. Min Piping Lengthm
Ref. Max Piping Lengthm50
Vertical Height Difference (Max)
*Outdoor Unit Above/Below Indoor Unit
m50 / 15
Refrigerant Amount Pre-charged (kg/TCO2Eq)3.3 / 2.228
* For Pipe Length Up Tom30
Additional Refrigerantg/m54